Table 3-2. Logic Operated Switch - CCI0 = 1
Step Module Input(s) Output(s) Comments
5 Datapoint
C005
C005 = B144 (ANI1)
6ANOs B100 = C005 (ANI1). ANO0 = B100 = ANI1.
If CCI0 = 0, the following event sequence occurs as described in Table 3-3:
Table 3-3. Logic Operated Switch - CCI0 = 0
Step Module Input(s) Output(s) Comments
1 ANI ANI1 (C021) and
ANI2 (C022).
2 Param D B143 = C021 (ANI1)
and B142 = L000,
which is 0 and inhibits
the output.
3 Logic A B127 = L000, which is
0 because CCI0 is
open.
L097 = 1. FC = 128 or A NOT;
therefore, a 0 in = a 1
out.
4 Param E B146 = C022 (ANI2)
and B145 = L097,
which is 1 because
CCI0 is open.
B147 = ANI2
5 Datapoint
C005
C005 = B147 (ANI2)
6ANOs B100 = C005 (ANI2). ANO0 = B100 = ANI2.
FCS 53MC5000 Flexible Control Strategies
3-6
EX2