2.7.39 ANALOG OUTPUT LOADER
The Analog Output (ANO0-4) Loader module has parameters which allow an FCS signal to be
scaled to the proper units before it is supplied to an analog output from the 53MC5000 Process
Control Station (PCS). Each ANO output value can be scaled with the following formula:
ANO
0-4
= [(C-value x Scaler) + Bias]
The table that follows lists the ANO0-4 C-value inputs with their respective SCALER and BIAS pa-
rameters that affect the module output values. The
POINTS TO
column in the table is used to list
the input C-values from the other FCS modules that are wired to the ANO B-datapoints. Also listed
in the table are the OZBASE parameters that indicate the type of analog outputs (0 = 4-20 mA, 1 =
0-20 mA) from the ANO module. An illustration of the ANO0-4 module follows the table.
ANO0-4 Module Parameters
ANO POINTER POINTS TO SCALER BIAS OZBASE
ANO0 B100 C C037 C038 L472
ANO1 B101 C C039 C040 L473
ANO2 B102 C C041 C042 L474
ANO3 B103 C C043 C044 L475
ANO4 B104 C C045 C046 L476
FCS 53MC5000 Flexible Control Strategies
2-56
ANALGOUT