2.7.38 LOGIC H
The Logic H module executes a selected function on two input variables A and B to produce an out-
put. Input variables A and B, as well as the output, are all logic values (0/1). The table below lists
the input variables; an illustration of the Logic H module follows the table. The function code (FC)
to be executed by the Logic H module is selected from the Logic Functions table at the bottom of
the page and entered into datapoint B239. The function codes are also provided in expanded form
on the next page.
Inputs
WIRELIST SYMBOL DATA
TYPE
ASSIGNED VALUE
B237 A L
B238 B L
B239 FC N/A
Output Datapoint:
L084
Logic Functions
FC OUTPUT FC OUTPUT
0A4A OR NOT B
1 A OR B 5 A AND NOT B
2 A AND B 6 J-K LATCH
3 A XOR B 7 D LATCH
Invert output if FC = FC + 128
FCS 53MC5000 Flexible Control Strategies
2-54
LOGC-H