Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Manuel d'utilisateur Page 16

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 201
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 15
2.7.2 CONTACT CLOSURE INPUT LOADER
The Contact Closure Input (CCI0-17) Loader module generates a logic level (0/1) L-value output
for each connected CCI depending on an applied voltage or the contact condition of its associated
terminals (e.g., for CCIs 0 and 1, the minimum open or closed recognition time is 0.05 seconds; 1
V dc maximum = closed contact recognition level; 4 - 24 V dc = open contact recognition level.
See specifications in Section 1 of 53MC5000 Instruction Bulletin for CCIs 2 -17).
The table that follows lists the CCI0-17 invert parameters and outputs. An illustration of the
CCI module follows the table.
CCI0-17 Module Parameters
CONTACT INVERT OUTPUT CONTACT INVERT OUTPUT
CCI0 L264 L000 CCI9 L273 L009
CCI1 L265 L001 CCI10 L274 L010
CCI2 L266 L002 CCI11 L275 L011
CCI3 L267 L003 CCI12 L276 L012
CCI4 L268 L004 CCI13 L277 L013
CCI5 L269 L005 CCI14 L278 L014
CCI6 L270 L006 CCI15 L279 L015
CCI7 L271 L007 CCI16 L280 L016
CCI8 L272 L008 CCI17 L281 L017
Section 2. FCS Modules
CCI117
2-9
Vue de la page 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 200 201

Commentaires sur ces manuels

Pas de commentaire