Micromod MOD: 30ML Functions Data Base Reference Manuel d'utilisateur Page 36

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 152
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 35
MOD 30ML Functions
DISPLAY INTERFACE BLOCK
05 Faceplate Comm Error (FPCOMS) .................................................................................. CWR
The error “FACEPLATE COMMUNICATIONS ERROR” (event code 4) is reported if an error
occurred when trying to communicate with the faceplate. Instances are counted in
CMERRCTR (attribute 30) or BFULLCTR (attribute 29).
ENABLED 0 Faceplate communication error is enabled.
SUPPRESSED 1 Faceplate communication error is suppressed.
06 Faceplate Communication Error Unacknowledged (FPCOMU)................................... – WR
If the faceplate communication error diagnostic is enabled, the unacknowledged status
indicates if the diagnostic is or is not acknowledged.
NO 0 Diagnostic error is acknowledged.
YES 1 Diagnostic error is unacknowledged (not writeable).
07 Faceplate Communication Error Active (FPCOMA) ...................................................... – – R
If the faceplate communication error diagnostic is enabled, the active status indicates if the
diagnostic is active even after acknowledgment.
NO 0 Diagnostic error is not active.
YES 1 Diagnostic error is active.
08 No Keyboard Response (NOKBDS) ................................................................................ CWR
The error “NO KEYBOARD RESPONSE”.(event code 5) is reported if the faceplate failed to
respond when keyboard data was requested. Instances are counted in KBERRCTR (attribute
31).
ENABLED 0 No Keyboard Response error is enabled.
SUPPRESSED 1 No Keyboard Response error is suppressed.
09 No Keyboard Response Unacknowledged
(NOKBDU) ................................................. – WR
If the no keyboard response error diagnostic is enabled, the unacknowledged status
indicates if the diagnostic is or is not acknowledged.
NO 0 Diagnostic error is acknowledged.
YES 1 Diagnostic error is unacknowledged (not writeable).
10 No Keyboard Response Active (NOKBDA) .................................................................... – – R
If the no keyboard response error diagnostic is enabled, the active status indicates if the
diagnostic is active even after acknowledgment.
NO 0 Diagnostic error is not active.
YES 1 Diagnostic error is active.
11 Reserved
12 Faceplate Version (FPVER) ............................................................................................ – – R
This is the software version of the faceplate presented as a number 0.0 to 25.5.
13 Device Tag (DEVTAG) ..................................................................................................... CWR
Up to 8 ascii characters identifying the instrument. Displayed on the second line of the top
level device display on the front panel of the instrument.
14 Power Up Display User Tag (PUPDISP) ........................................................................ CWR
2-28
Vue de la page 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 151 152

Commentaires sur ces manuels

Pas de commentaire