Single Loop Process Controller Instruction Manual
Configuration Parameters 53
No Byte
Stuffing
CB L2581 0
When set to a 1, this datapoint disables the
standard MicroMod communication protocol feature
which inserts a 00 (NUL) byte after every 7EH
(SOH) that is not the beginning of a message. (This
permits user-written communications software to
determine the number of bytes to expect in a
response message.) It must be set to 0 when using
MicroMod communications software or equipment.
Datalink
Disable
DLD L257
0
When set to 0, it permits full Datalink
communication capabilities. When set to 1, it
disables Datalink communication capabilities.
Table 4-11. System Module
Title Symbol
System
Module
Datapoint
Default Attribute
Purpose: Purpose: The primary purpose of this module is to select and initiate the instrument mode of
operation, and set the Scan Index.
Function Index
FIX B00
0
The operational algorithm of the unit is selected
by the value of this parameter:
0 = Suspend mode. No control algorithm
execution. The logo is displayed.
1 = CS1, Single Loop PID Controller operation
2 = CS2, Analog Backup Controller operation.
3 = CS3, Ratio Controller operation.
4 = CS4, Automatic/Manual Station operation.
97 = Display Test. The entire display alternately
flashes on and off. When off, a border around the
display perimeter remains lit.
98 = Defaults database then sets FIX to 0.
Display Brightness
Index
BRIGHT
B12 4
This parameter controls the display screen
intensity. A value of 0 is the brightest and a value
of 7 is the dimmest intensity. Normal viewing
setting is 4.
EASY-TUNE
Enable
ETE
B08 0
When set to a 1, the EASY-TUNE algorithm is
implemented. This parameter is left at 0 for
normal instrument operation. (See Section 11 for
EASY-TUNE.)
Unit Tag Name
TAG A08
SL5100
This is an assignable 10 character name for the
system module (SL5100).
Table 4-10. Communication Module (Continued)
Title Symbol
CCO0
Datapoint
Default Attribute