Single Loop Process Controller Instruction Manual
136 Database
ANI1
Calibrate
Zero
CIZ B264
This is the calibration zero adjustment. This parameter is
factory set and should not need adjustment under
normal operation. See Section 12.3 for adjustment.
ANO0
Calibrate
Zero
COZ B267
This is the calibration zero adjustment. This parameter is
factory set and should not need adjustment under
normal operation. See Section 12.3 for adjustment.
ANI0 Digital
Filter Index
DFILT B269
3
This controls a first order filter that is applied to the input
signal. The time constant is entered as an index value as
follows:
0 - No Smoothing (no effect)
1 - 0.05 s
2 - 0.1 s
3 - 0.3 s
4 - 0.7 s
5 - 1.5 s
6 - 3.1 s
7 - 6.3 s
8 - 12.7 s
9 - 25.5 s
10 - 51.1 s
11 - 102 s
12 - 205 s
13 - 410 s
14 - 819 s
15 - 1638 s
ANI1 Digital
Filter Index
DFILT B270
3
This controls a first order filter that is applied to the input
signal. The time constant is entered as an index value as
follows:
0 - No Smoothing (no effect)
1 - 0.05 s
2 - 0.1 s
3 - 0.3 s
4 - 0.7 s
5 - 1.5 s
6 - 3.1 s
7 - 6.3 s
8 - 12.7 s
9 - 25.5 s
10 - 51.1 s
11 - 102 s
12 - 205 s
13 - 410 s
14 - 819 s
15 - 1638 s
Table C-2. Database (Continued)
Title Symbol Datapoint Default Attribute