3.3.2 Erasing Steps
Selecting ERASE (pressing F3 when ERASE is displayed) causes the following line to appear:
n SURE? Y
Pressing F1 (i.e., selecting NO) just returns to the "ERASE" level.
Pressing F3 (i.e., selecting YES) causes all 100 steps to be set to F-CIM 42 which is a "do nothing"
module and sets B00 to 0 .
Pressing F1 returns to the VIEW level.
3.3.3 Building Steps
Selecting BUILD (pressing F3 when BUILD is displayed) causes a display line to appear at the
bottom of the display.
STEP?
The four arrow keys can now be used to indicate the step number that is to be edited. When the step
number is correct, pressing F3 causes the main editing screen to appear. The UP and DOWN arrows
can be used to scroll though the steps. The F1 key returns to BUILD level. The F2 key steps though
the REPLACE, INSERT, and DELETE sub-functions. F3 selects the sub-function being displayed.
REPLACE - Allows the currently displayed step to be edited.
INSERT - Moves the current step and all following steps down by one and allows the new current
step to be edited.
DELETE - Deletes the current step and shifts the following steps up. Automatically adjusts step
references.