AUTO/MANUAL SWITCH - 0
INPUTS NAME SYMBOL DATAPOINT
CONTROL OUTPUT CO0 C123
AUTO ENABLE AE0 L114
OUTPUT TRACK VALVE OTV0 C129
OUTPUT TRACK SWITCH SWOTV0 L117
PARAMETERS OUTPUT TRACK ENABLE OTE0 L119
HARD MANUAL LIMIT HML0 L122
OUTPUT HIGH LIMIT OH0 C109
OUTPUT LOW LIMIT OL0 C110
OUTPUT SLEW RATE T30 C118
OUTPUTS
OUTPUT OUT0 C102
OUTPUT TRACK STATUS OVTS0 L105
AUTO STATUS AUT0 L107
Description:
The AUTO/MAN Switch selects one of three signals to load into OUT. The signal
selected is either the Output Tracking Value (OTV), the Auto Value (CO) or the
Manual Pushbutton Value. If the Output Tracking Switch (SWOUT) is zero (0) then
OUT = OTV when Output Tracking is enabled (OTE = 1). When the previous
condition is not in effect OUT will equal CO if Auto Enable = 1 and the A/M
pushbutton has set the Auto Switch to 1. When neither previous condition is in effect
the selected signal comes directly from the output increase and decrease pushbut-
tons.