G14
AUTO/MANUAL SWITCH - 2
INPUTS NAME SYMBOL DATAPOINT
CONTROL OUTPUT CO2 C195
AUTO ENABLE AE2 L162
OUTPUT TRACK VALVE OTV2 C201
OUTPUT TRACK SWITCH SWOTV2 L165
PARAMETERS OUTPUT TRACK ENABLE OTE2 L167
HARD MANUAL LIMIT HML2 L170
OUTPUT HIGH LIMIT OH2 C181
OUTPUT LOW LIMIT OL2 C182
OUTPUT SLEW RATE T32 C190
OUTPUTS
OUTPUT OUT2 C174
OUTPUT TRACK STATUS OVTS2 L153
AUTO STATUS AUT2 L155
Description:
The AUTO/MAN Switch selects one of three signals to load into OUT. The signal
selected is either the Output Tracking Value (OTV), the Auto Value (CO) or the
Manual Pushbutton Value. If the Output Tracking Switch (SWOUT) is zero (0) then
OUT = OTV when Output Tracking is enabled (OTE = 1). When the previous
condition is not in effect OUT will equal CO if Auto Enable = 1 and the A/M
pushbutton has set the Auto Switch to 1. When neither previous condition is in effect
the selected signal comes directly from the output increase and decrease pushbut-
tons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE