Micro-PWC CONFIGURATION GUIDE
Grafx Editor 175
4.4.3.8 FP_DYputpbstat2
The submodel FP_DYputpbstat2 (Figure 4-51) is a pushbutton that, when pressed, writes values into up
to 4 controller database points. The button label changes color and an asterisk is displayed based on the
value of a controller database point. The following example shows an instance of FP_DYputpbstat2 config-
ured to put the CON module tcPID into AUTO mode when the button is "pressed" (clicked on). Additionally,
when the AUT atom of the controller is set, an asterisk (k) is displayed to the right of the label, and the label
"Auto" appears in red.
Position the pointer on the submodel and click the right mouse button, then click on the Configure Sub-
model item on the resulting pop-up menu. The Submodel Configuration window for the PUTPBSTAT2
Pushbutton Submodel will appear. Notice that this window (Figure 4-52) is scrollable and contains more
variables than those which appear in the display area. Use the scrollbar to access the additional variables
(Figure 4-53).
Figure 4-51. FP_DYputpbstat2 Submodel
Figure 4-52. FP_DYputpbstat2 Submodel Configuration Window, Part 1