SETUP
Table 3. Digital Input Setup Menu
Step Step Description
Top
Display
3.1
Digital Input 2 Function.
UP
or
DN
selects function.
SCRL
to advance to:
Step 4 from NONE, or
Step 3.1.1 from AUTO/MAN, or
Step 3.1.10 from ALRM ACK or OUTP TRK, or
Step 3.1.6 from TOTALIZE, or
Step 3.1.4 from RAMPSOAK, or
Step 3.1.8 from SETP SEL.
DIG IN 2
3.1.1
Digital Auto to Manual Fixed Output Enable.
UP
or
DN
selects YES or NO.
SCRL
to advance to:
Step 3.1.2 from NO, or
Step 3.1.1.1 from YES.
DIG A-M
3.1.1.1
Digital Auto to Manual Fixed Output Value.
UP
or
DN
sets value.
SCRL
to advance to Step 3.1.2.
DIG A-M
3.1.2
Auto/Manual Key Lockout.
UP
or
DN
selects YES or NO.
SCRL
to advance to Step 3.1.3.
A/M KEY
3.1.3
Manual to Auto Transition Allowed.
UP
or
DN
selects YES or NO.
SCRL
to advance to Step 3.1.10.
MAN-AUTO
3.1.4
Ramp/Soak Digital Input 2 Function.
UP
or
DN
selects function.
SCRL
to advance to Step 3.1.5.
RAMPSOAK