Micromod MOD: Modcell 2050R Users Guide Manuel d'utilisateur Page 114

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 228
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 113
IB-23C650
SETUP
Table 11. Alarm Settings Menu
Step Step Description
Top
Display
1
Alarms Menu.
UP
moves to TOTALIZE **MENU** if totalizer is
enabled, or to RAMPSOAK **MENU** if
ramp/soak is enabled, or to RAT BIAS
**MENU** if ratio bias is enabled, or to SETPTS
**MENU** otherwise.
DN
moves to TUNE **MENU**.
SCRL
to begin setup at Step 2.
ALARMS
2
Beep on Occurrence Of.
UP
or
DN
selects type.
SCRL
to advance to Step 3.
BEEP ON
3
Alarm Acknowledge Required.
UP
selects YES or
DN
selects NO.
SCRL
to advance to Step 4.
ALRM ACK
4
Overconfigured Diagnostic
UP
selects YES or
DN
selects NO.
SCRL
to advance to:
Step 5 if acknowledge is required on priority 1
process alarms, or
Step 6 if acknowledge is required on priority 2
process alarms, or
Step 7 otherwise.
OVERCFGD