Training Manual
Single Loop Template Lab
3 - 19
16 Press NXT HI QUAL is displayed on line 2. Result is set
BAD if it goes above this value. High quality must
be higher than the low quality value
17 Set line 6 at 220. Then press ENT
18 Press NXT until line 2 and 6 are blank
and
only the up arrow is on
19 Press UP
20 Press NXT This completes the Process Input section. SETPT