If HI/LO alarms are required, enter the following:
B335=0 (HI/LO alarm index)
C103=High alarm setpoint
C104=Low alarm setpoint
C105=Alarm deadband
Alarm setpoints and deadbands are in Engineering Units.
7. Configure the Control Module parameters for Loop #2:
Enter the 10-character loop tagname in A02 and the 7-character Engineering Units
in A03.
Set the tuning parameter if desired:
C142 = Proportional Band
C143 = Reset time in minutes per repeat
C144 = Derivative time in minutes
The 53MC5000 is set for reverse action. If direct action is required, enter L130=0.
If setpoint limits are desired, enter the setpoint high limit in C161 and the low limit
in C162. Both limits are in Engineering Units.
If output limits are desired, enter the output high limit in C145 and the low limit in
C146. Both limits are in percent of output. Output limits are active in both Auto and
Manual mode.
If HI/LO alarms are required, enter the following:
B340=0 (HI/LO alarm index)
C139=High alarm setpoint
C140=Low alarm setpoint
C141=Alarm deadband
Alarm setpoints and deadbands are in Engineering Units. Other alarm types are available (see In-
struction Bulletin 53MC5000 Section 4.1.6).
MODULAR CONTROLLER QUICK START
4-10