Micromod RetroPAK: SLC Configuration Manual Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Micromod RetroPAK: SLC Configuration Manual. Micromod RetroPAK: SLC Configuration Manual User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 394
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs

Résumé du contenu

Page 1 - Training

Command Series Migration to MOD 30ML™ Training Tutorial and Reference Guide for Command Series Migration to MOD 30ML

Page 2 - MicroMod Automation, Inc

Command Series Migration to MOD 30ML Function Codes – Introduction The user database is configurable and writable to make the instrument perform

Page 3 - CONTENTS

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the Algorithm Type (S18): Open the PID block and open the C

Page 4

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the Control Action (S21): Open the PID block and open the G

Page 5

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To enable Setpoint Tracking (FC21-S14): Open the PID block and open t

Page 6

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control Notice that the only setpoint mode allowed is LOCAL: Figure P1.14. P

Page 7 - INTRODUCTION

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the process variable high alarm (FC21-S7): Open the PAD blo

Page 8

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the process variable low alarm (FC21-S8): Open the PAD bloc

Page 9 - Function Codes – Introduction

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control a Refer to the following sections from the Function Codes – Gallery

Page 10 - Environment Blocks:

Pre-configured Dual Loop PID Control GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral derivati

Page 11

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control EXPLANATION Configuration with this compound requires understanding of

Page 12 - Architecture

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control S11 PID Input – S11 Floating Point Gain Multiplier input for the PID.

Page 13 - FUNCTION BLOCKS

Command Series Migration to MOD 30ML Function Codes – Introduction Display Interface Block(DIF): This block is used in MOD 30ML only. This block h

Page 14

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control N PID Output – N Floating Point Output of the compound. PID.N is alre

Page 15

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To configure the inputs: Open the AIN block AIN1 for input 1. See figu

Page 16

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control Figure P2.3. Dual loop PID with Local SP You will need to use a diff

Page 17 - Function blocks

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the display tag name for the PID: Open the display block PID

Page 18 - Execution Order

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To enable feedforward control and change the feedforward type (S6): Op

Page 19 - COMPOUNDS:

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To connect / change the value of the Gain Multiplier input (S11): Make

Page 20 - Bailey FC Gallery

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the value of the Manual Reset input (S5): To enter a local va

Page 21 - Choose Parameter

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the values of the following: Proportional Gain - S12 Integral

Page 22 - Cancel Connection

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the value of the Derivative Lag Constant (S15): Open the PID

Page 23 - LOOP COMPOUNDS

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the value of the Output Limits (S16, S17): Open the PID block

Page 24 - Algorithms menu

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .1. Instrument Database Architecture 1 - 4

Page 25

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the Algorithm Type (S18): Open the PID block and open the Con

Page 26 - THE CONFIGURATION PROCESS

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the Control Action (S21): Open the PID block and open the Gen

Page 27 - PID Display

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To enable Setpoint Tracking (FC21-S14): Open the PID block and open the

Page 28 - DIF block

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control Notice that the only setpoint mode allowed is LOCAL: Figure P2.14. Dua

Page 29

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the process variable high alarm (FC21-S7): Open the PAD block

Page 30 - PID CONFIGURATION REFERENCE

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control To change the process variable low alarm (FC21-S8): Open the PAD block

Page 31 - PID Control Tab

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID Control a Refer to the following sections from the Function Codes – Gallery Tu

Page 32

Pre-configured Single Loop PID with Remote SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral

Page 33

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP EXPLANATION Configuration with this compound requires underst

Page 34 - PID Setpoint Tab

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP compound or change in the Control tab of the PID block. Change

Page 35 -  Output Modes in MOD 30ML:

Command Series Migration to MOD 30ML Function Codes – Introduction I/O AND COMMUNICATION MODULE BLOCKS: These blocks specify the physical I/O comp

Page 36 - PID Options Tab

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP S23 N/A N/A N/A SPTI PID Input – Floating Point Setpoint t

Page 37 - GALLERY TUTORIAL

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To configure the inputs: Open the AIN block AIN1 for input 1.

Page 38

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP Figure P3 .3. PID with Remote SP You will need to use a dif

Page 39 - OBJECTIVES

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the display tag name for the PID: Open the display

Page 40 - DOCUMENT

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To enable feedforward control and change the feedforward type

Page 41 - New Workspace

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To connect / change the value of the Gain Multiplier input (S1

Page 42

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the value of the Manual Reset input (S5): To enter a

Page 43 - New Project

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the values of the following: Proportional Gain - S12

Page 44 - Class Workspace

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the value of the Derivative Lag Constant (S15): Open

Page 45 - New Document

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the value of the Output Limits (S16, S17): Open the

Page 46 - Default Instrument

Command Series Migration to MOD 30ML Function Codes – Introduction Type Description Availability Input Function Blocks or signal conditioning

Page 47

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the Algorithm Type (S18): Open the PID block and ope

Page 48 - Interface Block

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the Control Action (S21): Open the PID block and ope

Page 49 - CLC 03/04

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To enable Setpoint Tracking (FC21-S14): Open the PID block and

Page 50 - Properties

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP Remote Setpoint Configuration Options: Open the PID block and

Page 51

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP Auto Bias: Bias value of remote setpoint is automatically man

Page 52 - Open Compound

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the process variable high alarm (FC21-S7): Open the

Page 53 - Compound

Command Series Migration to MOD 30ML Pre-configured Single Loop PID with Remote SP To change the process variable low alarm (FC21-S8): Open the P

Page 54 - Loop Block

Pre-configured Dual Loop PID with Remote SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral d

Page 55 - Gallery Menu

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP reference that includes listing of most commonly used / changed

Page 56

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP S10 N/A N/A N/A S11 PID Input – S11 Floating Point Gain Mult

Page 57

Command Series Migration to MOD 30ML Function Codes – Introduction NM Notification Message MOD 30ML and Modcell SM Supervisory Message MOD 30M

Page 58 - ADDING I/O

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP S21 PID Input – Discreet Controller Action. Choose the action

Page 59 - AIN Block

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To configure the inputs: Open the AIN block AIN1 for input 1. S

Page 60 - VCI Properties

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP Figure P4.3. Dual PID with Remote SP You will need to use a

Page 61

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP Figure P4.4. Dual PID with Remote SP P4- 7

Page 62 - MAKING CONNECTIONS

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the display tag name for the PID: Open the display bl

Page 63 - Choose parameter

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To enable feedforward control and change the feedforward type (S

Page 64

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To connect / change the value of the Gain Multiplier input (S11)

Page 65

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the value of the Manual Reset input (S5): To enter a l

Page 66

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the values of the following: Proportional Gain - S12 I

Page 67

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the value of the Derivative Lag Constant (S15): Open t

Page 68 - SP) Compound

Command Series Migration to MOD 30ML Function Codes – Introduction A typical instrument database as function block diagram configured in ViZapp i

Page 69 - ENG block

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the value of the Output Limits (S16, S17): Open the PI

Page 70

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the Algorithm Type (S18): Open the PID block and open

Page 71 - Faceplate

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the Control Action (S21): Open the PID block and open

Page 72 - 100. See the next figure:

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To enable Setpoint Tracking (FC21-S14): Open the PID block and o

Page 73

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP Remote Setpoint Configuration Options: Open the PID block and s

Page 74 - Close Compound

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP Auto Bias: Bias value of remote setpoint is automatically manip

Page 75

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the process variable high alarm (FC21-S7): Open the PA

Page 76

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP To change the process variable low alarm (FC21-S8): Open the PAD

Page 77

Command Series Migration to MOD 30ML Pre-configured Dual Loop PID with Remote SP a Refer to the following sections from the Function Codes – Gal

Page 78 - SAVING DOCUMENTS

Pre-Configured – Cascade Control GENERAL DESCRIPTION This is a pre-configured loop compound that has inputs, outputs, complete Cascade loop PI

Page 79

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .3. Function blocks inside a loop compound 1 - 9

Page 80 - Communication

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control EXPLANATION Configuration with this loop compound requires understanding o

Page 81 - COMPILING THE DATABASE

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control GAIN MULTIPLIER INPUT. S11 PID2 Input – S11 Floating Point Gain Multiplie

Page 82 - Options for Modbus

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control S18 PID1, PID2, PIDFAIL Input – S18 Count Algorithm Type. Choose the type

Page 83 - Information Window

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To configure the inputs: Open the AIN block AIN1 for input 1. See figure b

Page 84

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control Figure P5.3. Cascade PID You will need to use a different input function

Page 85 - STRATEGIES

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the display tag name for the PID: Open the display block Display

Page 86

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To enable feedforward control and change the feedforward type (S6): Open t

Page 87

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To connect / change the value of the Gain Multiplier input (S11): Make a co

Page 88

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the value of the Manual Reset input (S5): To enter a local value,

Page 89

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the values of the following: Proportional Gain - S12 Integral Res

Page 90

Command Series Migration to MOD 30ML Function Codes – Introduction FUNCTION BLOCK EXECUTION ORDER: The order in which the blocks in the database

Page 91

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the value of the Derivative Lag Constant (S15): Open the respecti

Page 92

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the value of the Output Limits (S16, S17): Open the respective PI

Page 93

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the Algorithm Type (S18): Open the respective PID block and open

Page 94

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the Control Action (S21): Open the respective PID block and open

Page 95

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To enable Setpoint Tracking (FC21-S14): Open the respective PID block and o

Page 96

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the process variable high alarm (FC21-S7): Open the desired PAD b

Page 97

Command Series Migration to MOD 30ML Pre-Configured – Cascade Control To change the process variable low alarm (FC21-S8): Open the desired PAD bl

Page 98

Pre-configured PID Ratio with Remote SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral deriv

Page 99

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP reference that includes listing of most commonly used / changed attr

Page 100 - PID with Local SP

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP S12 ENG Input – GAIN Floating Point Proportional Gain Kp. Enter in

Page 101 - See figure below:

Command Series Migration to MOD 30ML Function Codes – Introduction COMPOUNDS: Function blocks in a database can be compounded (grouped) into a si

Page 102

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP N PID Output – N Floating Point Output of the compound. PID.N is a

Page 103

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To configure the inputs: Open the AIN block AIN1 for input 1. See f

Page 104

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP Figure P6.3. PID Ratio with Remote SP You will need to use a dif

Page 105

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the display tag name for the PID: Open the display block

Page 106

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To enable feedforward control and change the feedforward type (S6):

Page 107 - UTILIZATION

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To connect / change the value of the Gain Multiplier input (S11): Ma

Page 108 - INPUTS – OUTPUTS

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the value of the Manual Reset input (S5): To enter a local

Page 109

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the values of the following: Proportional Gain - S12 Integ

Page 110

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the value of the Derivative Lag Constant (S15): Open the P

Page 111 - Dual loop

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the value of the Output Limits (S16, S17): Open the PID bl

Page 112

MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving customer efficiency by providing the most cost-effective, applic

Page 113 - Display Block

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .6. Inside a Compound • You can ungroup a compound by un-compoundin

Page 114

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the Algorithm Type (S18): Open the PID block and open the

Page 115

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the Control Action (S21): Open the PID block and open the

Page 116

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To enable Setpoint Tracking (FC21-S14): Open the PID block and open

Page 117

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP Remote Setpoint Configuration Options: Open the PID block and select

Page 118

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP Auto Bias: Bias value of remote setpoint is automatically manipulat

Page 119

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the process variable high alarm (FC21-S7): Open the PAD bl

Page 120

Command Series Migration to MOD 30ML Pre-configured PID Ratio with Remote SP To change the process variable low alarm (FC21-S8): Open the PAD blo

Page 121

BOOK 2 REFERENCE SECTION 2 FUNCTION CODE COMPOUNDS

Page 123

Function Code 1- Function Generator GENERAL DESCRIPTION This function approximates a nonlinear output to input relationship. The input range i

Page 124

Command Series Migration to MOD 30ML Function Codes – Introduction • This will un-group the function blocks and place them where the grouped comp

Page 125

Command Series Migration to MOD 30ML Function Code 1- Function Generator Figure 1 .2.Function Generator compound INPUTS - OUTPUTS INPUTS - OUT

Page 126

Function Code 2- Manual Set Constant GENERAL DESCRIPTION The output of the Manual Set Constant or the Signal Generator is an analog signal dev

Page 127

Command Series Migration to MOD 30ML Function Code 2- Manual Set Constant Millisecond time Format: hh:mm:ss.xxx (xxx in millisecond) Hex Hexadec

Page 128 - INPUTS - OUTPUTS

Command Series Migration to MOD 30ML Error! No text of specified style in document. APPLICATIONS This compound is meant for storing of values that

Page 129

Command Series Migration to MOD 30ML Function Code 2- Manual Set Constant 2 - 4

Page 130

Function Code 3 - Lead / Lag GENERAL DESCRIPTION The output of a lead/lag function code equals the product of the time function and the input

Page 131 - PID with Remote

Command Series Migration to MOD 30ML Function Code 3 - Lead / Lag EXPLANATION Function code 3 causes the output of the function block to lead or

Page 132

Command Series Migration to MOD 30ML Function Code 3 - Lead / Lag Lag Function : To select the lag function, leave S3 at its initial value (0) and

Page 133

Command Series Migration to MOD 30ML Function Code 3 - Lead / Lag 3 - 4

Page 134

Function Code 6 – High / Low Limiter GENERAL DESCRIPTION This block limits the output signal to a range that lies between a specified high and

Page 135

Command Series Migration to MOD 30ML Function Codes – Introduction • You can also double-click on the Compound Internals and then select from th

Page 136

Command Series Migration to MOD 30ML Function Code 6 – High / Low Limiter 6 - 2

Page 137

Function Code 7 – Square Root GENERAL DESCRIPTION This function computes the square root of the input signal in engineering units. The output

Page 138

Command Series Migration to MOD 30ML Function Code 7 – Square Root N Output – R Floating Point Connect from the FC7.N signal of the compound.

Page 139

Command Series Migration to MOD 30ML Function Code 7 – Square Root Figure 7 .3. LN block used for linearizing 7 - 3

Page 140

Command Series Migration to MOD 30ML Function Code 7 – Square Root 7 - 4

Page 141

Function Code 8 – Rate Limiter GENERAL DESCRIPTION The output of this block equals the input until the input rate of change exceeds the limit

Page 142

Command Series Migration to MOD 30ML Function Code 8 – Rate Limiter INPUTS - OUTPUTS Signal Block Type Description S1 RATELIM Input – S1 Floa

Page 143

Command Series Migration to MOD 30ML Function Code 8 – Rate Limiter To verify this, check the execution order of the blocks. Select Objects – Set

Page 144

Command Series Migration to MOD 30ML Function Code 8 – Rate Limiter To change the Increase Rate Limit S3: Open the EX block INCLIM. Select the In

Page 145

Command Series Migration to MOD 30ML Function Code 8 – Rate Limiter Figure 8 .5. Blocks Execution Order after rearranging 8 - 5

Page 146 - Low Alarm

Command Series Migration to MOD 30ML Function Codes – Introduction LOOP COMPOUNDS Loop compound is a special compound that contains a loop block.

Page 147

Command Series Migration to MOD 30ML Function Code 8 – Rate Limiter 8 - 6

Page 148

Function Code 9 – Analog Transfer GENERAL DESCRIPTION This function selects one of two inputs depending on Boolean input <S3>. The outpu

Page 149

Command Series Migration to MOD 30ML Function Code 9 – Analog Transfer S2 S1/S2 Input – S2 Floating Point Connect to the S1/S2.S2 signal of the

Page 150

Command Series Migration to MOD 30ML Function Code 9 – Analog Transfer Figure 9 .2. Blocks Execution Order You can change the execution order of

Page 151 - Remote SP

Command Series Migration to MOD 30ML Function Code 9 – Analog Transfer Figure 9 .4. Timer block S4 To change the transfer time (S5) for S2: Ope

Page 152

Command Series Migration to MOD 30ML Function Code 9 – Analog Transfer Figure 9 .5. Timer Block S5 9 - 5

Page 153

Command Series Migration to MOD 30ML Function Code 9 – Analog Transfer 9 - 6

Page 154

Function Code 10 – High Select GENERAL DESCRIPTION This function selects and outputs the input with the highest algebraic value. UTILIZATION

Page 155

Command Series Migration to MOD 30ML Function Code 10 – High Select S4 FC10 Input – S4 Floating Point Connect to the FC10.S4 signal to the Hig

Page 156

Function Code 11 – Low Select GENERAL DESCRIPTION This function selects and outputs the input with the lowest algebraic value. UTILIZATION Th

Page 157

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .13. Cancel Connection To add a loop compound: Select the Loop Cpd (

Page 158

Command Series Migration to MOD 30ML Function Code 11 – Low Select N FC11 Output – R Floating Point Connect from the FC11.N output signal from

Page 159

Function Code 12 – High / Low Compare GENERAL DESCRIPTION This function has two outputs. When the input is equal to or exceeds the high limit,

Page 160

Command Series Migration to MOD 30ML Function Code 12 – High / Low Compare INPUTS - OUTPUTS Input Block Type Description S1 HIGHLIM Input –

Page 161

Command Series Migration to MOD 30ML Function Code 12 – High / Low Compare NOTES To change the High alarm point / high limit: Open the HIGHLIM exp

Page 162

Command Series Migration to MOD 30ML Function Code 12 – High / Low Compare Figure 12 .3. High Select Function Inputs 12 - 4

Page 163

Function Code 14 - Summer GENERAL DESCRIPTION This function computes the algebraic sum of up to four inputs with unity gain. The output equati

Page 164 - Hi Alarm

Command Series Migration to MOD 30ML Function Code 14 - Summer Figure 14 .2. Function Code 14 Input Configuration INPUTS - OUTPUTS Signal Bloc

Page 165

Function Code 15 – Summer (2 Inputs) GENERAL DESCRIPTION This function performs a weighted sum of two inputs. By choosing the proper gains and

Page 166

Command Series Migration to MOD 30ML Function Code 15 – Summer (2 Inputs) Figure 15 .2. Function Code 15 INPUTS - OUTPUTS Signal Block Type

Page 167

Function Code 16 – Multiply GENERAL DESCRIPTION This function performs a multiplication of two input signals (S1 by S2) with the result multip

Page 168

Command Series Migration to MOD 30ML Function Codes – Introduction • Loop compounds also have jump objects when connections are made from or to t

Page 169

Command Series Migration to MOD 30ML Function Code 16 – Multiply Figure 16 .2. Function Code 16 INPUTS - OUTPUTS Signal Block Type Descripti

Page 170

Function Code 17 – Divide GENERAL DESCRIPTION This function causes one input S1 to be divided by a second input S2 and the quotient to be mult

Page 171

Command Series Migration to MOD 30ML Function Code 17 – Divide Figure 17 .2. Function Code 17 INPUTS - OUTPUTS Signal Block Type Description

Page 172

Function Code 20 – Indicator Station GENERAL DESCRIPTION This function displays 3 inputs in one display one at a time. UTILIZATION The MOD

Page 173 - Cascade PID

Command Series Migration to MOD 30ML Function Code 20 – Indicator Station Figure 20 .2. Function Code 14 Input Configuration Add the Display

Page 174

Command Series Migration to MOD 30ML Error! No text of specified style in document. Figure 20 .3. Closing Compound • Click on the New button on t

Page 175

Command Series Migration to MOD 30ML Function Code 20 – Indicator Station • A text edit box will appear in the area below and you will see a te

Page 176

Command Series Migration to MOD 30ML Error! No text of specified style in document. INPUTS - OUTPUTS Signal Block Type Description S1 DISPLAY

Page 177

Command Series Migration to MOD 30ML Function Code 20 – Indicator Station 20 - 6

Page 178

Function Codes 25 and 41 – Analog/Digital Input GENERAL DESCRIPTION This function can be used to acquire an input (analog, digital or any othe

Page 179

Command Series Migration to MOD 30ML Function Codes – Introduction THE CONFIGURATION PROCESS The steps involved configuring a MOD 30ML or Modcell

Page 180

Command Series Migration to MOD 30ML Function Codes 25 and 41 – Analog/Digital Input   To configure the ICN communication in an instrument data

Page 181

Command Series Migration to MOD 30ML Function Codes 25 and 41 – Analog/Digital Input Figure 25 .3. Function Code 25 and 41 To configure the sourc

Page 182

Command Series Migration to MOD 30ML Function Codes 25 and 41 – Analog/Digital Input Figure 25 .4. IC Block INPUTS - OUTPUTS Signal Block Typ

Page 183

Function Code 28 – Analog/Digital Output GENERAL DESCRIPTION This function can be used to send an output (analog, digital or any other data ty

Page 184

Command Series Migration to MOD 30ML Function Code 28 – Analog/Digital Output   To configure the ICN communication in an instrument database, y

Page 185

Command Series Migration to MOD 30ML Function Code 28 – Analog/Digital Output Instrument Number – This is the ICN address of the instrument wher

Page 186 - Low Alarm

Command Series Migration to MOD 30ML Function Code 28 – Analog/Digital Output 28 - 4

Page 187

Function Code 33 – NOT GENERAL DESCRIPTION Function code 33 performs a logical negation of the input (the output is the opposite of the input)

Page 188

Command Series Migration to MOD 30ML Function Code 33 – NOT 33 - 2

Page 189

Function Code 34 – Memory (RS Flip Flop) GENERAL DESCRIPTION This function memorizes its previous output when both inputs are logic 0. S1 is t

Page 190

Command Series Migration to MOD 30ML Function Codes – Introduction Procedure for adding the Display Tag to the Display Interface Block Each displa

Page 191 - PID Ratio with

Command Series Migration to MOD 30ML Function Code 34 – Memory (RS Flip Flop) Figure 34 .2. Function Code 34 S3 INPUTS - OUTPUTS Truth Table f

Page 192

Function Code 35 – Timer GENERAL DESCRIPTION The timer function code performs pulsed timing function. The duration of time delay is specified

Page 193

Command Series Migration to MOD 30ML Function Code 35 – Timer Figure 35 .2. Function Code 35 S3 INPUTS – OUTPUTS Signal Block Type Descript

Page 194

Command Series Migration to MOD 30ML Error! No text of specified style in document. EXPLANATION I/O Elapsed Time < S3 Elapsed Time > S3 IN

Page 195

Command Series Migration to MOD 30ML Function Code 35 – Timer 35 - 4

Page 196

Function Code 36 – Qualified OR GENERAL DESCRIPTION The qualified OR function code monitors the status of up to eight digital inputs and produ

Page 197

Command Series Migration to MOD 30ML Function Code 36 – Qualified OR To specify the value of S9, open the EX block and click on the Inputs tab. D

Page 198

Command Series Migration to MOD 30ML Function Code 36 – Qualified OR Figure 36 .3. INPUTS - OUTPUTS Signal Block Type Description S1 FC36

Page 199

Command Series Migration to MOD 30ML Function Code 36 – Qualified OR S7 FC36 Input – S7 Boolean (Discrete) Connect to the FC36.S7 signal of the

Page 200

Function Code 37 – AND (2 input) GENERAL DESCRIPTION The 2-input AND function code performs the logical AND function. The output is logic 1 wh

Page 201

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .16. DIF block Click on the New button on this block as shown in fig

Page 202

Command Series Migration to MOD 30ML Function Code 37 – AND (2 input) Truth Table Figure 37 .2. Function Code 37 Truth Table 37 - 2

Page 203

Function Code 38 – AND (4 input) GENERAL DESCRIPTION The 4-input AND function code performs the logical AND function. The output is logic 1 wh

Page 204

Command Series Migration to MOD 30ML Function Code 38 – AND (4 input) N FC38 Output – R Boolean (Discrete) Connect from the FC.38.N signal of t

Page 205

Function Code 39 – OR (2 input) GENERAL DESCRIPTION The 2-input OR function code performs the logical OR function. The output is logic 1 if ei

Page 206

Command Series Migration to MOD 30ML Function Code 39 – OR (2 input) 39 - 2

Page 207 - FUNCTION CODE COMPOUNDS

Function Code 40 – OR (4 input) GENERAL DESCRIPTION The 4-input OR function code is used to perform the logical OR function. The output is log

Page 208

Command Series Migration to MOD 30ML Function Code 40 – OR (4 input) Truth Table Figure 40 .2. Function Code 40 Truth Table 40 - 2

Page 209

Function Code 51- Manual Set Constant GENERAL DESCRIPTION The output of the Manual Set Constant or the Signal Generator is an analog signal de

Page 210 - APPLICATIONS

Command Series Migration to MOD 30ML Function Code 51- Manual Set Constant INPUTS - OUTPUTS Signal Type Block Description S1 Input – S1 Float

Page 211

Function Code 59- Digital Transfer GENERAL DESCRIPTION This function code selects one of two digital inputs, depending on a transfer switch si

Page 212

Command Series Migration to MOD 30ML Function Codes – Introduction A text edit box will appear in the area below and you will see a text edit curs

Page 213

Command Series Migration to MOD 30ML Function Code 59- Digital Transfer 59 - 2

Page 214

Function Code 65 – Digital Sum with Gain GENERAL DESCRIPTION This function computes the weighted sum of up to four Boolean inputs. The output

Page 215 - Function Code 3 - Lead / Lag

Command Series Migration to MOD 30ML Function Code 65 – Digital Sum with Gain Figure 65 .2. Function Code 65 Input Configuration INPUTS - OUTP

Page 216

Command Series Migration to MOD 30ML Function Code 65 – Digital Sum with Gain S6 FC65 Input gain parameter – S6 Floating Point Connect to the F

Page 217

Command Series Migration to MOD 30ML Function Code 65 – Digital Sum with Gain 65 - 4

Page 218

Function Code 156 – PID with Local SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral derivat

Page 219

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP EXPLANATION Configuration with this compound requires understanding o

Page 220

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP GAIN to change the value. S13 ENG Input – RESET Floating Point Integra

Page 221 - Function Code 7 – Square Root

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP S23 N/A N/A N/A SPTI PID Input – Floating Point Setpoint track inp

Page 222 - VCI block used for

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To enable feedforward control and change the feedforward type (S6): Ope

Page 223 - LN block used for

Command Series Migration to MOD 30ML CONTENTS CONTENTS Page BOOK 1 SECTION 1 – FUNCTIONCODES - INTRODUCTION HOW TO USE THIS BOOK ...

Page 224

Command Series Migration to MOD 30ML Function Codes – Introduction PID CONFIGURATION REFERENCE The PID block in the MOD 30ML/Modcell is versatile

Page 225

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To connect / change the value of the Gain Multiplier input (S11): Make

Page 226

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the value of the Manual Reset input (S5): To enter a local val

Page 227 - Order after

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the values of the following: Proportional Gain - S12 Integra

Page 228

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the value of the Derivative Lag Constant (S15): Open the PID b

Page 229

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the value of the Output Limits (S16, S17): Open the PID bloc

Page 230

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the Algorithm Type (S18): Open the PID block and open the Cont

Page 231

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the Control Action (S21): Open the PID block and open the Ge

Page 232

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To enable Setpoint Tracking (FC21-S14): Open the PID block and open the

Page 233

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP Notice that the only setpoint mode allowed is LOCAL: Figure 156 .12.

Page 234 - Timer block S4

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the process variable high alarm (FC21-S7): Open the PAD block

Page 235 - Timer Block S5

Command Series Migration to MOD 30ML Function Codes – Introduction Figure 1 .20. PID Control Tab • Select the Algorithm Type and change it to ES

Page 236

Command Series Migration to MOD 30ML Function Code 156 – PID with Local SP To change the process variable low alarm (FC21-S8): Open the PAD block

Page 237

Function Code 156 – PID (Cascade) GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral derivative

Page 238

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) EXPLANATION Configuration with this compound requires understanding of th

Page 239 - Function Code 11 – Low Select

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) of the PID2 block. Change the value for GAIN MULTIPLIER INPUT. S11 PIDFA

Page 240

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) S19 N/A N/A N/A S21 PID1, PID2, PIDFAIL Input – S21 Discreet Controller

Page 241

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the display tag name for the PID: Open the display block Displ

Page 242

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To enable feedforward control and change the feedforward type (S6): Open

Page 243 - Function Inputs

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To connect / change the value of the Gain Multiplier input (S11): Make a

Page 244

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the value of the Manual Reset input (S5): To enter a local value

Page 245 - Function Code 14 - Summer

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the values of the following: Proportional Gain - S12 Integral R

Page 246

Command Series Migration to MOD 30ML Function Codes – Introduction M 8 MICRO-SCAN. Reset response is turned on and is operating with MICRO-SCAN a

Page 247

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the value of the Derivative Lag Constant (S15): Open the respect

Page 248

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the value of the Output Limits (S16, S17): Open the respective

Page 249 - Function Code 16 – Multiply

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the Algorithm Type (S18): Open the respective PID block and open

Page 250

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the Control Action (S21): Open the respective PID block and ope

Page 251 - Function Code 17 – Divide

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To enable Setpoint Tracking (FC21-S14): Open the respective PID block and

Page 252

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the process variable high alarm (FC21-S7): Open the desired PAD

Page 253

Command Series Migration to MOD 30ML Function Code 156 – PID (Cascade) To change the process variable low alarm (FC21-S8): Open the desired PAD b

Page 254 - Configuration

Function Code 156 – PID with Remote SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral deriva

Page 255 - Closing Compound

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP EXPLANATION Configuration with this compound requires understanding

Page 256

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP Floating Point GAIN to change the value. S13 ENG Input – RESET Flo

Page 257 - OPERATION

Command Series Migration to MOD 30ML Function Codes – Introduction  The valid actions for CATYPE are: EOOO Gain on error, Reset off, Pre-Act of

Page 258

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP N PID Output – N Floating Point Output of the compound. Connect fro

Page 259

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the display tag name for the PID: Open the display block

Page 260 - Function Code 25

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To enable feedforward control and change the feedforward type (S6):

Page 261

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To connect / change the value of the Gain Multiplier input (S11): Ma

Page 262

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the value of the Manual Reset input (S5): To enter a local

Page 263

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the values of the following: Proportional Gain - S12 Integ

Page 264 - Function Code 28

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the value of the Derivative Lag Constant (S15): Open the PI

Page 265

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the value of the Output Limits (S16, S17): Open the PID bl

Page 266

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the Algorithm Type (S18): Open the PID block and open the C

Page 267 - Function Code 33 – NOT

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the Control Action (S21): Open the PID block and open the

Page 268

Command Series Migration to MOD 30ML Function Codes – Introduction • Click on the Setpoint tab to select the Setpoint configuration options. See

Page 269

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To enable Setpoint Tracking (FC21-S14): Open the PID block and open t

Page 270

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP Remote Setpoint Configuration Options: Open the PID block and selec

Page 271 - Function Code 35 – Timer

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP Auto Bias: Bias value of remote setpoint is automatically manipulate

Page 272

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the process variable high alarm (FC21-S7): Open the PAD bl

Page 273

Command Series Migration to MOD 30ML Function Code 156 – PID with Remote SP To change the process variable low alarm (FC21-S8): Open the PAD bloc

Page 274

Function Code 156 – PID Ratio with Remote SP GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral

Page 275

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP reference that includes listing of most commonly used / changed

Page 276 - Function Code 36

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP Floating Point Inputs tab and select the input RESET to change

Page 277

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the display tag name for the PID: Open the display b

Page 278

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To enable feedforward control and change the feedforward type

Page 279

Command Series Migration to MOD 30ML Function Codes – Introduction • Click on the Output tab to select the output configuration options. See the

Page 280 - Truth Table

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To connect / change the value of the Gain Multiplier input (S11

Page 281

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the value of the Manual Reset input (S5): To enter a

Page 282

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the values of the following: Proportional Gain - S12

Page 283

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the value of the Derivative Lag Constant (S15): Open

Page 284

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the value of the Output Limits (S16, S17): Open the P

Page 285

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the Algorithm Type (S18): Open the PID block and ope

Page 286

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the Control Action (S21): Open the PID block and open

Page 287

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To enable Setpoint Tracking (FC21-S14): Open the PID block and

Page 288

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP Remote Setpoint Configuration Options: Open the PID block and s

Page 289

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP Auto Bias: Bias value of remote setpoint is automatically man

Page 290

Command Series Migration to MOD 30ML Function Codes – Introduction block or it can be an internal value in the PID block that can be manually cha

Page 291

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP To change the process variable high alarm (FC21-S7): Open the P

Page 292

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP Figure 156rr .15. Process Variable Low Alarm PID Ratio with R

Page 293

Command Series Migration to MOD 30ML Function Code 156 – PID Ratio with Remote SP 156rr - 18

Page 294

Function Code 156 – PID with Manual/Auto Station GENERAL DESCRIPTION The PID with Manual/Auto station function basically performs Manual / Aut

Page 295

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station EXPLANATION Configuration with this compound requires unde

Page 296

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station S12 M/A Input – GAIN Floating Point Proportional Gain Kp. E

Page 297 - 156 - 3

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To change the display tag name for the PID: Open the displ

Page 298 - Function Code

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To enable feedforward control and change the feedforward type

Page 299

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To connect / change the value of the Gain Multiplier input

Page 300

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To change the value of the Manual Reset input (S5): To enter

Page 301

BOOK 1 SECTION 2 GALLERY TUTORIAL

Page 302

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To change the value of the Derivative Lag Constant (S15): O

Page 303

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To change the value of the Output Limits (S16, S17): Open the

Page 304

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station To change the Control Action (S21): Open the PID block and

Page 305

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station Note that the OP (Output) of the PID block is connected to th

Page 306

Command Series Migration to MOD 30ML Function Code 156 – PID with Manual/Auto Station Notice that the only setpoint mode allowed is REMOTE: Figur

Page 307

Function Code 156 – Auto Bias Station GENERAL DESCRIPTION The PID with Auto Bias Station is basically a Manual/Auto station that performs Manu

Page 308

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station EXPLANATION Configuration with this compound requires understanding o

Page 309

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station MULTIPLIER INPUT. S12 AUTO BIAS Input – GAIN Floating Point Proport

Page 310

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To change the display tag name for the PID: Open the display block PI

Page 311

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To enable feedforward control and change the feedforward type (S6):

Page 313

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To connect / change the value of the Gain Multiplier input (S11): Make

Page 314

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To change the value of the Manual Reset input (S5): To enter a local

Page 315

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To change the values of the following: Proportional Gain - S12 Integra

Page 316

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To change the value of the Derivative Lag Constant (S15): Open the PI

Page 317

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station To change the value of the Output Limits (S16, S17): Open the PID bloc

Page 318

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station Note that the OP (Output) of the PID block is connected to the SPTI (

Page 319

Command Series Migration to MOD 30ML Function Code 156 – Auto Bias Station Notice that the only setpoint mode allowed is REMOTE: Figure 156ab .10

Page 320

Function Code 165 - Moving Average GENERAL DESCRIPTION The moving average function code computes a moving average from n samples taken at a de

Page 321

Command Series Migration to MOD 30ML Function Code 165 - Moving Average INPUTS - OUTPUTS Signal Type Block Description S1 Input – S1 Floating

Page 322

BOOK 2 REFERENCE SECTION 3 EXTRAS

Page 323

Function Codes – Gallery Tutorial FOREWORD The ViZapp (Visual Application Designer) software has a library of function block compounds that rep

Page 325

Extras – Reject to Manual GENERAL DESCRIPTION The Reject to Manual compound sends a logical Zero output when its digital input does a low to h

Page 326

Command Series Migration to MOD 30ML Extras – Reject to Manual INPUTS - OUTPUTS Signal Type Block Description S1 Input – S1 Discrete QUALLOGI

Page 328

The Company’s policy is one of continuous product improvement and the right is reserved to modify the information

Page 329

Command Series Migration to MOD 30ML CONTENTS BOOK 2 – FUNCTION CODE GALLERY COMPOUNDS REFERENCE SECTION 1 – PRE-CONFIGURED CONTROL STRATEGIES 1

Page 330 - Floating Point

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial INSTRUCTIONS – CREATING A NEW WORKSPACE, PROJECT AND DOCUMENT 1. Launch Vi

Page 331

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .3. New Workspace • By default, the workspace file is created i

Page 332

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial  • The New dialog box will redisplay Figure 2 .5. New Workspace • T

Page 333

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial • Notice that the workspace Class is added to the project tree. We will cr

Page 334

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .9. Class Workspace • The left frame shows the project tree. T

Page 335

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .10. New Document • The New dialog box shows the Document tab no

Page 336

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .11. Choose Instrument Version • Select MOD 30ML 2 from this li

Page 337

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial  Each instrument will have its own database. The databases of the instrum

Page 338

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial CONFIGURING SCAN GROUPS AND LOOP COMPOUNDS 5. Let us first configure a sc

Page 339

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial M/A Station – Function Code 21 Analog output AO – Function Code 29 Figure 2

Page 340

Command Series Migration to MOD 30ML CONTENTS 20 FUNCTION CODE 35 – TIMER...

Page 341

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial • Select the Loop Cpd (Loop compound) block from the Algorithms window ad

Page 342

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial • Type a description "This compound is for the Flow Control Loop"

Page 343

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .19. Open Compound • The loop compound will open as shown below

Page 344

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .20. Inside the Loop Compound  A loop compound is a compound or

Page 345

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .21. Loop Block • Close the Loop block by clicking on the OK bu

Page 346

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial ADDING COMPOUND FROM THE GALLERY 11. We will now use a compound from the B

Page 347

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .23. Bailey FC Gallery • The compounds in this gallery have be

Page 348

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .24. Bailey FC Gallery • The exported compound will be placed in

Page 349

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial ADDING I/O 12. The loaded compound has all the function blocks for doing t

Page 350

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial • Resize the block by dragging one of the handles (corner or side) Figure

Page 351

Command Series Migration to MOD 30ML CONTENTS iv

Page 352

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial • The next function block VCI, is a signal conditioning block. This block

Page 353

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .29. PID Options Tab • Click on OK to accept the changes and clo

Page 354

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial MAKING CONNECTIONS 15. The next step is to connect the blocks together.

Page 355

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .33. Connecting blocks • The connection will now be complete. Th

Page 356

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .35. Right Angle connection • Click on the output point of the

Page 357

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .37. Choose Parameter • Select PID.S1 from the list and then cli

Page 358

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .39. Cancel Connection 17. Connect the PID output from the com

Page 359

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .41. 2 - 29

Page 360 - High Alarm

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial CHANGING ENGINEERING RANGES AND ALARM TRIP VALUES 18. The FC156 PID (PV/L

Page 361

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .44. ENG block • Select the Inputs tab of this block. Double-cl

Page 362

BOOK 1 SECTION 1 FUNCTION CODES – INTRODUCTION

Page 363

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .45. ENG block • Repeat the above process to configure the Low

Page 364

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial  If you press the ALARM key on the faceplate when the alarm is active, th

Page 365 - 156ma - 3

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial CONFIGURING DISPLAY TAG FOR THE PID DISPLAY 19. Each display configured i

Page 366

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .48. PID Display • Click on OK to close the block. 2 - 35

Page 367

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial 20. Close the compound: • First click on a blank area of the function b

Page 368

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial 21. Add the Display Tag to the Display Interface Block: The next step is t

Page 369

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .52. Closing Compound • A text edit box will appear in the are

Page 370

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .53. Closing Compound • Refer back to the figure 1-37 for the di

Page 371

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial SAVING DOCUMENTS 22. Save your Document. Figure 2 .54. File Menu • I

Page 372

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial SETTING UP COMMUNICATIONS WITH MODBUS 23. We need to setup communications f

Page 374

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial  The connections for the port are available in the terminals in the back

Page 375

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial COMPILING THE DATABASE It is necessary to compile the database without erro

Page 376

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .60. Interface File Options for Modbus • If the database has er

Page 377

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial Figure 2 .61. Information Window • You can double-click on an error to o

Page 378 - Auto Bias Station

Command Series Migration to MOD 30ML Function Codes – Gallery Tutorial 2 - 46

Page 379

BOOK 2 REFERENCE SECTION 1 PRE-CONFIGURED CONTROL STRATEGIES

Page 381

Pre-configured Single Loop PID Control GENERAL DESCRIPTION The advanced PID controller function code implements a proportional integral deriva

Page 382

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control EXPLANATION Configuration with this compound requires understanding

Page 383

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control of the PID block. Change the value for GAIN MULTIPLIER INPUT. S12 EN

Page 384

Function Codes – Introduction HOW TO USE THIS BOOK This book is meant for users of Bailey SLC, CLC controllers who are migrating to the new gen

Page 385

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control the first loop. S22 N/A N/A N/A S23 N/A N/A N/A SPTI PID Input

Page 386

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To configure the inputs: Open the AIN block AIN1 for input 1. See fi

Page 387

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control Figure P1.3. PID with Local SP You will need to use a different in

Page 388

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the display tag name for the PID: Open the display block P

Page 389 - SECTION 3

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To enable feedforward control and change the feedforward type (S6):

Page 390

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To connect / change the value of the Gain Multiplier input (S11): Mak

Page 391 - Extras – Reject to Manual

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the value of the Manual Reset input (S5): To enter a local

Page 392

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the values of the following: Proportional Gain - S12 Integr

Page 393

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the value of the Derivative Lag Constant (S15): Open the PI

Page 394

Command Series Migration to MOD 30ML Pre-configured Single Loop PID Control To change the value of the Output Limits (S16, S17): Open the PID blo

Commentaires sur ces manuels

Pas de commentaire