Command Series Migration to MOD 30ML
Function Code 11 – Low Select
N FC11 Output – R
Floating Point
Connect from the FC11.N output
signal from the Low Selector.
APPLICATIONS
The most common use of function code 10 is to select the lowest value. You can also use
this compound for finding the lowest value for 2 or 3 inputs by setting a fixed value for
the unused inputs. This value can typically be a very high value that is higher than the
highest value the connected inputs can assume.
Configuration of the inputs is shown in the next figure:
Figure 11 .2.
Low Select
Function Inputs
11 - 2