MOD 30ML Display Guide
Display Basics
2 -3
Connections between the appropriate algorithm blocks and the Display and Tune blocks
have already been made in the compounds. In most cases the user must make minor
modifications to the blocks within the compound, or add to the State Table block.
Instructions are provided in READ or NOTES blocks within each Symbol.
The default ranges for PID blocks are 0 to 100 per cent, with local setpoint (the
Cascade allows Local/Remote on the Slave). Change ranges by opening the blocks
and making the appropriate entries. Default values for tuning parameters are Gain =
1.0, Reset = 0.01, Preact Off. New tuning values can be entered in the PID block
during strategy configuration, or entered from the front panel after download.
Any of the compounds may be used as a basis for a custom display.