53SL5100B Single-Loop Controller
INSTRUCTION MANUAL
21
3.3 Displaying a Datapoint
The following procedure illustrates how to enter Engineering Mode (EMODE) and use the display function to
access the contents of datapoint A001 (A1). The displayed contents will be PERCENT. Figure 3-9 and Figure
3-10 are supporting illustrations for the display procedure which is described in Table 3-2. It should be noted
that EMODE has a 20 second timeout if it is accessed and its functions (e.g., configure or display) are not
used.
Table 3-2. Procedures to Display a Datapoint
Step Press
Once
Shift
Result
Press to
Locate
Target
Char.
Result
1
MODE
Puts instrument in engineering mode.
2
If CONFIGURE appears instead of DISPLAY, press F2.
3
F3
Displays entry line: POINT .
4
A
Puts A on entry line: POINT .A.
5
.AΔ
1
Shifts A and puts 1 on entry line: POINT .A1.
6
F3
Enters address to display datapoint contents.
The address and the contents are displayed as
follows: A1 PERCENT.
7
MODE
Returns instrument to operator mode.
NOTE:
Δ = space.
Figure 3-9. POINT.A1 Figure 3-10. A1 PERCENT